Viessmann Vitomax 200 - LW
Description
Type M241, oil/gas fired low pressure hot water boiler.
Rated output: 7.8 to 19.5 MW. Permissible operating
pressure: 6/10 bar. Permissible flow temperature:
110/120 °C.
The Vitomax 200-LW benefits at a glance:
- Economical fuel consumption – boiler efficiency: 92%
- Three-pass boiler with low combustion chamber loading (1.3 MW/m3) – clean combustion with low nitrogen oxide emissions
- No minimum heating water flow rate required – wide water galleries and large water content provide excellent natural circulation and a reliable heat transfer –simplified hydraulic connection
- No additional intermediate flow piece required. All necessary connections for a safety temperature of 110 ºC are already fitted to the boiler
- Low pressure drop on the hot gas side through convection heating surfaces with generously sized hot gas pipes
- High level of serviceability through water-cooled reversing chambers without lining and large boiler doors
- Low radiation losses through 120 mm thick composite thermal insulation
- Load bearing cover on top of the boiler as part of the standard delivery – this simplifies the installation and maintenance and protects the thermal insulation against accidental damage
- The Vitocontrol control panel enables the regulation of all boiler-specific control equipment
- Approval in accordance with the European Pressure Equipment Directive 97/23/EC or the Gas Equipment Directive 90/396/EEC